Energy Efficiency in the Refrigeration and Air-Conditioning Sector

Refrigerants and substitutes

If you operate refrigeration or air-conditioning equipment, some of the refrigerants in it are already banned from import and others fall under a shrinking annual quota. Here you can see what replaces what, what the law requires, and who to turn to.

Banned or restricted → Approved GWP · AR4
Current refrigerant
HFC blend · GWP 2,088
Under annual quota
blend: R-32 / R-125 · boiling -51.4 °C

Operates at roughly 60% higher pressure than R-22 and therefore requires equipment designed for it. Dominant in split air conditioning from the 2000s onwards.

Split and multi-split air conditioning.

Approved substitutes (3)
  • R-32 A2L GWP lower by 68%
    difluoromethane · GWP 675
    Split air conditioners and heat pumps
    Manual §2.5.2
  • R-454B A2L GWP lower by 78%
    low-GWP blend · GWP 466
    Split and multi air conditioning
    Manual §2.5.2
  • R-452B A2L GWP lower by 67%
    low-GWP blend · GWP 698
    Unitary systems
    Manual §2.5.2

Replacement must be carried out by a certified technician. Class A2L and A3 refrigerants are flammable and require specific installation conditions.

Full list of refrigerants

Banned 3 Phase-out 3 Under quota 5 Approved 17

CodeName FamilyGWPODP ClassBoiling CompositionStatus
R-22 HCFC-22 HCFC 1,810 0.06 A1 -40.8 °C single-component HCFC Phase-out
R-404A HFC blend HFC 3,922 0 A1 -46.5 °C blend: R-125 / R-143a / R-134a Under quota
R-410A HFC blend HFC 2,088 0 A1 -51.4 °C blend: R-32 / R-125 Under quota
R-134a HFC-134a HFC 1,430 0 A1 -26.1 °C single-component HFC Under quota
R-407C HFC blend HFC 1,774 0 A1 -43.6 °C blend: R-32 / R-125 / R-134a Under quota
R-507A HFC blend HFC 3,985 0 A1 -47.1 °C azeotropic blend: R-125 / R-143a Under quota
R-32 difluoromethane HFC 675 0 A2L -51.7 °C single-component HFC Approved
R-454B low-GWP blend HFO/HFC 466 0 A2L -50.9 °C blend: R-32 / R-1234yf Approved
R-452B low-GWP blend HFO/HFC 698 0 A2L -51.0 °C blend: R-32 / R-125 / R-1234yf Approved
R-449A blend HFC 1,397 0 A1 -46.0 °C blend: R-32 / R-125 / R-1234yf / R-134a Approved
R-448A blend HFC 1,387 0 A1 -45.9 °C blend: R-32 / R-125 / R-1234yf / R-1234ze / R-134a Approved
R-455A low-GWP blend HFO/HFC 146 0 A2L -51.6 °C blend: CO₂ / R-32 / R-1234yf Approved
R-513A blend HFO/HFC 631 0 A1 -29.2 °C azeotropic blend: R-1234yf / R-134a Approved
R-1234yf HFO HFO 4 0 A2L -29.5 °C single-component HFO Approved
R-1234ze(E) HFO HFO 7 0 A2L -19.0 °C single-component HFO Approved
R-290 propane natural 3 0 A3 -42.1 °C propane, C₃H₈ Approved
R-600a isobutane natural 3 0 A3 -11.7 °C isobutane, C₄H₁₀ Approved
R-744 carbon dioxide natural 1 0 A1 -78.4 °C carbon dioxide, CO₂ Approved
R-717 ammonia natural 0 0 B2L -33.3 °C ammonia, NH₃ Approved
R-152a HFC-152a HFC 124 0 A2 -24.0 °C single-component HFC Approved
R-11 trichlorofluoromethane CFC 4,750 1 A1 23.8 °C CFC-11, trichlorofluoromethane Banned
R-12 dichlorodifluoromethane CFC 10,900 1 A1 -29.8 °C CFC-12, dichlorodifluoromethane Banned
R-113 trichlorotrifluoroethane CFC 6,130 0.80 A1 47.6 °C CFC-113, trichlorotrifluoroethane Banned
R-123 dichlorotrifluoroethane HCFC 77 0.02 B1 27.8 °C HCFC-123, dichlorotrifluoroethane Phase-out
R-124 chlorotetrafluoroethane HCFC 609 0.02 A1 -12.0 °C HCFC-124, chlorotetrafluoroethane Phase-out
R-454A low-GWP blend HFO/HFC 238 0 A2L -48.6 °C blend: R-32 / R-1234yf Approved
R-454C low-GWP blend HFO/HFC 148 0 A2L -45.6 °C blend: R-32 / R-1234yf Approved
R-1270 propylene natural 2 0 A3 -47.6 °C propylene, C₃H₆ Approved

All GWP values follow AR4. Source: Manual on energy efficiency of RAC systems, May 2026.